jpf4826-rs
This project is a cross-platform command-line tool for JPF4826 fan controller by modbus protocol.
binary name is jpf4826ctl
Global Options
-p, --port=PORT
Specify PORT to connect to the JPF4826 controller.
Required: Yes (unless JPF4826_PORT environment variable is set)
Examples:
- Linux:
/dev/ttyUSB0 - macOS:
/dev/tty.usbserial-XXXXXXXX - Windows:
COM3
If not provided, falls back to the JPF4826_PORT environment variable.
-a, --addr=ADDR
Specify the Modbus address of the controller.
Range: 1-254 (hexadecimal 0x0001 to 0x00FE)
Required: Yes (unless JPF4826_ADDR environment variable is set)
If not provided, falls back to the JPF4826_ADDR environment variable.
-t, --timeout=TIMEOUT
Specify the timeout for each Modbus operation in seconds.
Range: 1-300 seconds
Default: 10 seconds
If not provided, falls back to the JPF4826_TIMEOUT environment variable, or uses the default of 10 seconds.
This timeout prevents indefinite waiting when the controller is not responding (e.g., wrong address or disconnected device).
--help
Display available commands and usage information.
Output
Control JPF4826 fan controller via Modbus-RTU
Usage: jpf4826ctl [OPTIONS] <COMMAND>
Commands:
status Display controller status
set Set controller registers
reset Reset the controller
help Print this message or the help of the given subcommand(s)
Options:
-p, --port <PORT> Serial port (falls back to JPF4826_PORT env var) [env: JPF4826_PORT=]
-a, --addr <ADDR> Modbus address (falls back to JPF4826_ADDR env var) [env: JPF4826_ADDR=]
-v, --verbose Enable verbose logging (debug output)
-t, --timeout <TIMEOUT> Timeout for each operation in seconds (1-300) [env: JPF4826_TIMEOUT=] [default: 10]
-h, --help Print help
-V, --version Print version
--version
Output
Display version.
Commands
status
Show current status of controller.
jpf4826ctl status
Options
-
--json: Output as JSON -
--temp-unit: Temperature unit0: Celsius1: Fahrenheit
-
--help: Display help for status command
Help Output
Display controller status
Usage: jpf4826ctl status [OPTIONS]
Options:
--json Output in JSON format
--temp-unit <TEMP_UNIT> Temperature unit (0=Celsius, 1=Fahrenheit)
-h, --help Print help
Output
Normal
ECO Mode True
Modbus Address 0x0001
PWM Frequency 25000 Hz
Fan Quantity 4
Temperature 26 ℃
Low Threshold 27 ℃
High Threshold 40 ℃
Fan Status
1
Status Normal
Speed (RPM) 1400
2
Status Fault
Speed (RPM) 0
3
Status Normal
Speed (RPM) 1400
4
Status Normal
Speed (RPM) 1400
JSON
Schema: schemas/jpf4826-status-response.schema.json
{
"eco_mode": true,
"modbus_address": 1,
"pwm_frequency": {
"value": 25000,
"unit": "Hz"
},
"fan_count": 4,
"temperature": {
"current": {
"value": 26,
"unit": "CELSIUS"
},
"low_threshold": {
"value": 27,
"unit": "CELSIUS"
},
"high_threshold": {
"value": 40,
"unit": "CELSIUS"
}
},
"fans": [
{
"index": 1,
"status": "NORMAL",
"rpm": 1400
},
{
"index": 2,
"status": "FAULT",
"rpm": 0
},
{
"index": 3,
"status": "NORMAL",
"rpm": 1400
},
{
"index": 4,
"status": "NORMAL",
"rpm": 1400
}
]
}
set
Set registers of controller by arguments
jpf4826ctl set \
--modbus-addr=5 \
--low-temp=25 \
--high-temp=38 \
--eco=1 \
--fan-qty=3 \
--pwm-freq=5000
Options
--help: Display help for set command
Help Output
Set controller registers
Usage: jpf4826ctl set [OPTIONS]
Options:
--auto-speed Switch to automatic temperature mode
--modbus-addr <MODBUS_ADDR> Modbus address (1-254)
--low-temp <LOW_TEMP> Start temperature threshold (-20 to 120°C)
--high-temp <HIGH_TEMP> Full speed temperature threshold (-20 to 120°C)
--eco <ECO> ECO/work mode (0=Minimum speed, 1=Shutdown)
--fan-qty <FAN_QTY> Number of fans (1-4, 0=disable fault detection)
--pwm-freq <PWM_FREQ> PWM frequency (500, 1000, 2000, 5000, 10000, 25000 Hz)
--manual-speed <MANUAL_SPEED> Manual speed percentage (0-100, switches to manual mode)
-h, --help Print help
Option Details
-
--auto-speed: Switch to automatic temperature mode- Boolean flag (no value needed)
- Switches controller to temperature-based automatic speed control
- Cannot be used together with
--manual-speed - Maps to register 0x0003 (writes 0xFFFF for temperature mode)
-
--modbus-addr: Modbus address of the controller- Range:
1-254 - Maps to register
0x0002
- Range:
-
--low-temp: Start temperature threshold (°C)- Range:
-20to120 - Fan starts spinning at this temperature
- Maps to register
0x000C(stored with +40 offset)
- Range:
-
--high-temp: Full speed temperature threshold (°C)- Range:
-20to120 - Fan reaches 100% speed at this temperature
- Must be greater than
--low-temp - Maps to register
0x000D(stored with +40 offset)
- Range:
-
--eco: ECO mode / Work mode0: Shutdown mode (fan stops completely below low_temp - 3°C)1: Minimum speed mode (fan maintains 20% speed below low_temp - 3°C)- Maps to register
0x0005
-
--fan-qty: Number of fans connected- Range:
1-4 - Set to
0to disable fault detection - Maps to register
0x0006
- Range:
-
--pwm-freq: PWM frequency in Hz- Valid values:
500,1000,2000,5000,10000,25000 - Default:
25000Hz - Maps to register
0x000B
- Valid values:
-
--manual-speed: Manual speed percentage- Range:
0-100 - Automatically switches controller to manual mode
- Disables temperature-based control
- Cannot be used together with
--auto-speed - Maps to register
0x0003(writes speed percentage value)
- Range:
reset
Reset the controller.
jpf4826ctl reset
Dependencies